Product Detailed

1,Material:PtRh30-PtRh,PtRh10-Pt,NiCr-NiSi,NiCr-CuNi,Cu-CuNi
2.Use temperature:0-1600
3.Standard:IEC584,GB/T16839
4.ISO9001

 Thermocouple-assembly type

 

1. BRIEF DESCRIPTION

Assembly type thermocouple which is used in industry as the sensor measuring temperature is generally connected with 

displaymeter, recording meter and electronic regulator to directly measure temperature of liquid, vapor, gas and solid 

surface ranging from 0 °C to 1800 °C during various production process. According to national regulation, the 

thermocouples with all kinds of graduation produced by our company conform to IEC international standard. Products 

executive standard : IEC 584, IEC1515 GB/T16839-1997 

 

2. THERMOCOUPLE TYPE&MEASURING RANGE

When the temperature appears step change, the output of thermocouple changes to about 5% of this change. And the 

time needed is called thermal response time, using T0.5 to express. 

 

3.TECHNICAL FEATURES

Nominal pressure of thermocouple 

Generally it refers to static outside pressure the protection tube can stand while not being broken in operation 

temperature. In fact tolerant operation pressure is not only related to protection tube material, diameter and the

thickness of wall but also related to its structure, mounting method, insert length and the flow velocity and type of 

measured medium. 

 

Minimum insert length of thermocouple 

It should be not less than 8 to 10 times of protectional tube outlet caliber (special products are exceptional). 

Insulation resistance of thermocouple (normal temperature) 

The testing voltage of insulation resistance at normal temperature is 500VΦ0V DC. 
The atmosphere condition measuring insulation resistance at normal temperature 
should be at temperature ranging from15-35°C , with 45% relative humidity and 86-

106 kPa atmospheric pressure. 

a.  For  the  thermocouple  whose  length  exceeds  one  meter  the  multiple  of  its normal-temperature insulation resistance and its length should be not less than 100 Mohm.m. That is : Rr.L ≥ 100 Mohm.m L> 1m,In  the  formula:  Rr -  insulation  resistance  value  of  thermocouple  at  normal temperature, Mohm

L - the length of thermocouple, m 

b.  For the thermocouple whose length is no more than one meter, its insulation resistance value at normal temperature 

should be not less than 100 Mohm. Insulation resistance at upper-limit temperature

Insulation resistance of thermocouple at upper-limit temperature should be not less 

than the stipulation in the below sheet: 

 

MODEL SELECTION SHEET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 



Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.